Fire Control

Glass is now firmly established as a fire protection material worldwide. Advances in glass products and manufacturing technology mean that today’s range of fire resistant glasses offer the architect and specifier the ability to create a beautiful and safe environment for all of us. At first glance it would seem that glass is not the ideal material for forming a barrier to fire. It has a reputation for being fragile and unable to cope with localised stresses. So, although it is incombustible and makes no contribution to the fire itself, on exposure to heat it breaks at relatively low temperatures, falling from its framing and allowing the passage of fire.

By selecting one of our fire resistant glasses these natural tendencies can be fully overcome.

Please find below a guide to selecting fire resistant glass:

Step Requirement Option Solution

0

Vertical Glazing

Go to 1

 
Sloping or horizontal glazing Go to 13

1

Integrity only required

Go to 2

 
Insulation and integrity required Go to 10
2 Period of fire resistance - 30 mins Go to 3  
Period of fire resistance - 60 mins Go to 7
Period of fire resistance - 90 mins Go to 8
Period of fire resistance - 120 mins Go to 8
3 Wires are acceptable Go to 4  
Unwired glass required   10mm Pyrodur
4 Safety glass is required for the location Go to 5  
Safety glass is not required Go to 6
5 Clear vision is required   Pyroshield safety clear
Obscuration is required   Pyroshield safety texture
6 Clear vision is required   Pyroshield clear
Obscuration is required   Pyroshield texture
7 Wires are acceptable Go to 4  
Unwired glass required   14mm Pyrodur
8 Timber frames   Not possible
Steel frames Go to 9  
9 Wires are acceptable Go to 5  
Unwired glass required Go to 10  
10 Period of fire resistance - 30 mins   15mm Pyrostop **
Period of fire resistance - 60 mins   21mm Pyrostop **
Period of fire resistance - 90 mins Go to 11  
Period of fire resistance - 120 mins Go to 12  
11 Timber frames   Not possible
Steel frames   44mm Pyrostop insulating unit**
12 Timber frames   Not possible
Steel frames   50mm Pyrostop insulating unit**
13 Period of fire resistance - 30 mins Go to 14  
Period of fire resistance - 60 mins   28mm Horizontal Pyrostop *
Period of fire resistance - 90 mins   Not possible
Period of fire resistance - 120 mins   Not possible
14 Integrity only required   Pyroshield Insulating unit
Integrity and insulation required   22mm Horizontal Pyrostop *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Horizontal version is either 15 or 21mm Pilkington Pyrostop with 6mm Pilkington Toughened Safety Glass laminated to the upper surface.

For internal applications only

** External grade Pilkington Pyrostop must be used if daylight or sunlight can strike the glass.



 